Plumbing & Water · Calculator
Water Service Pipe Size Calculator
Enter the fixture-unit load of the house, the lowest static pressure at the meter and the length of pipe to the farthest fixture. The calculator follows the simplified method in Appendix E of the International Plumbing Code and reads Table E104.1 for the service pipe, the meter and the main distribution pipe to the building.
Water service pipe and meter
3/4 in.
- Available pressure
- 52.5 psi
- How it was found
- 60 psi − 7.5 for elevation
- Pressure range
- 50 to 60 psi
- Length used
- 100 ft × 1.2 = 120 ft
- Table column
- 150 ft (next column up)
- Main distribution pipe to the building
- 1 in.
- That row carries up to
- 25 w.s.f.u. at this length
The length with the 20% allowance falls between two columns of the table, so the calculator reads the next longer one.
Branches are sized the same way, segment by segment from the farthest outlet back, but never need to be larger than the main (step 5 of E104.1).
2021 IPC Appendix E, Section E104.1 and Table E104.1.
For 20 water supply fixture units, 52.5 psi of available pressure and 120 ft of design length, Table E104.1 gives a 3/4 in. water service pipe and meter and a 1 in. main to the building.
What the table sizes
Table E104.1 gives the minimum size of the water meter and service pipe, and of the main distribution pipe to the building, from three figures: the load in water supply fixture units (w.s.f.u.), the pressure available and the longest developed length of pipe. It comes in four parts by pressure, 30 to 39 psi, 40 to 49, 50 to 60 and over 60, each with length columns from 40 to 500 ft.
Appendix E is part of the International Plumbing Code, but its provisions are not mandatory unless the adopting ordinance references them, and the code accepts other design methods that follow acceptable engineering practice and that the code official approves. The residential code, in Section P2903.7, sets the same 3/4-inch minimum for the water service pipe and also leaves the method to approved engineering practice, pointing to its own Appendix AP. We have not compared that appendix with this one.
The pressure you actually have
The method starts from the minimum daily static pressure at the meter or other source, the figure the local water authority can give you, and adjusts it in four ways:
- Height. Deduct 0.5 psi for each foot the highest water outlet sits above the source, or add 0.5 psi per foot if it sits below.
- A pressure-reducing valve. With one in the system, the pressure to start from is 80 percent of the static pressure at the source or the valve's set pressure, whichever is smaller.
- Equipment. Deduct the pressure lost through a backflow preventer, a water filter or a softener, from the manufacturer's data.
- Special fixtures. Where a fixture such as a temperature-controlled shower or a flushometer-tank toilet needs more than 8 psi, deduct the part above 8 psi.
The result picks the pressure range of the table. The ranges are written in whole numbers, so a pressure with decimals stays in the lower range until it reaches the first number of the next one: 39.5 psi reads as 30 to 39. Below 30 psi the table gives nothing.
Length, with 20 percent for fittings
The developed length is the actual length of pipe from the source to the most remote fixture, through the water heater if that fixture is on the hot side. The method multiplies it by 1.2 to account for the pressure lost in fittings and then uses the length column equal to or greater than the result. Beyond 500 ft the table stops.
Reading the table
Going down the chosen length column, the first row whose fixture-unit value is equal to or greater than the load gives the answer: the meter and service pipe size in the first column, and the main distribution pipe to the building in the second. A note to the table sets 3/4 inch as the minimum size for the building supply, so the calculator never gives a 1/2-inch main.
A few cells look odd: at over 60 psi, the 1-inch meter with a 1-inch main carries 28 w.s.f.u. at both 200 and 250 ft and then 17 at 300 ft, and the 2-inch row with a 2-inch main carries 365 at 40 ft and 368 from 60 ft. The 2012 and the 2021 editions print them the same way, and the calculator uses them as printed.
A worked example
A house totals 20 w.s.f.u. The water utility reports a minimum static pressure of 60 psi at the meter, the highest shower is 15 ft above it, and the farthest fixture is 100 ft of pipe away.
- Pressure: 60 − 7.5 for the height = 52.5 psi, in the 50 to 60 psi part of the table.
- Length: 100 × 1.2 = 120 ft, so the 150 ft column.
- Down that column, the first row that carries 20 w.s.f.u. or more is the 3/4-inch meter with a 1-inch main, good for 25.
The house needs a 3/4-inch water service and meter and a 1-inch main to the building.
Branch lines
The same table sizes the distribution branches, in a fifth step: start at the most remote outlet on each branch and work back toward the main, adding up the hot or cold fixture units that pass through each segment, and read each segment's size from the distribution column of the same length column, under the same or the next smaller meter row. No branch needs to be larger than the main. This calculator does the service, the meter and the main; for the branches, follow the table by hand.
Where the fixture units come from
The load is the total of the combined fixture-unit column of Table E103.3(2). Our water supply fixture units calculator uses the residential code's Table P2903.6, which gives the same combined values for the fixtures both tables list: 3.6 for a bathroom group with a tank toilet, 1.4 for a kitchen sink, a bathtub, a shower or a clothes washer, 0.7 for a lavatory and 2.2 for a tank toilet. The residential table also lists groups, such as a half bath or a laundry group, that Table E103.3(2) does not.
Questions people ask
What size water line do I need for my house?
It depends on the fixture-unit load, the pressure and the length of the run. In the worked example, 20 w.s.f.u. with 52.5 psi available and 100 ft of pipe needs a 3/4-inch service and meter and a 1-inch main. More fixtures, lower pressure or a longer run push the sizes up.
Is a 3/4-inch water service big enough?
It is the minimum the code allows, and Table E104.1 never gives less. Whether it is enough depends on the load, the pressure and the length: in the 50 to 60 psi range, a 3/4-inch meter and service with a 1-inch main carries 32 w.s.f.u. up to 100 ft of design length, but only 8 at 500 ft.
Does a pressure-reducing valve change the pipe size?
It can. With a valve, the method starts from 80 percent of the static pressure or the valve's set pressure, whichever is smaller: a 70 psi supply with a valve set to 60 psi counts as 56 psi. A lower pressure range can call for a larger pipe.
How much pressure is lost going up to a second floor?
Section E104.1 deducts 0.5 psi for every foot the highest outlet sits above the water source, so an outlet 10 ft higher than the meter costs 5 psi.
Sources
- 2021 International Plumbing Code, Appendix E: Sizing of Water Piping System (UpCodes, Colorado Plumbing Code 2021) — Section E104.1 and Table E104.1; Table E103.3(2), combined fixture units
- 2012 International Plumbing Code (Public.Resource.Org) — Section E201.1 and Table E201.1, used to check the 2021 procedure and every cell of the table
- 2021 Seattle Residential Code, Chapter 29: Water Supply and Distribution — Section P2903.7 and Table P2903.6