Water Supply Fixture Units Calculator

Count the bathrooms, the kitchen and the outdoor faucets. The calculator adds up their water supply fixture units with the values in the residential code and turns the total into the peak flow the pipes have to carry.

Toilet, sink and a tub or shower stall, counted as one group.

Toilet and sink.

Sinks without a dishwasher next to them.

Beyond the ones in the bathrooms above, such as a second sink in a full bath.

Homes almost always have tank toilets. Flushometer valves are the tankless kind found in commercial restrooms.

Water supply fixture units

18.7 w.s.f.u.

2 × full bathroom (3.6 each)
7.2
1 × half bathroom (2.6 each)
2.6
1 × kitchen with dishwasher (2.5 each)
2.5
1 × clothes washer (1.4 each)
1.4
2 × hose bibb (2.5 each)
5
Hot / cold
6.4 / 14.9

Peak demand: 19.2 gpm (Table P2903.6(1), 19 fixture-unit row, the next row up, tank toilets).

Values from IRC 2021 Table P2903.6 (combined column). A planning check, not a stamped design.

A water supply fixture unit is the code's way of weighting a fixture by how much water it draws and how often. A house with 2 full baths, 1 half bath, a kitchen with a dishwasher, a washer and 2 hose bibbs comes to 18.7 fixture units, which the IRC demand table turns into 19.2 gallons per minute.

What a fixture unit measures

A fixture unit is not a flow rate. It is a weight that combines how much water a fixture uses with how likely it is to be running at the same moment as everything else. A toilet tank refilling, a shower and a kitchen faucet all draw water, but rarely all at once, and the code's numbers build that in.

That is why a bathroom counted as a group is worth less than its parts. In IRC Table P2903.6 a tank toilet is 2.2 fixture units, a lavatory 0.7 and a bathtub 1.4, which adds up to 4.3. The same three fixtures counted as a full-bath group are 3.6, because one person in one bathroom uses them one after the other.

Groups or single fixtures

Count a room as a group when it matches the code's description, and count the extras one by one:

  • Full-bath group: toilet, sink and a bathtub or shower stall, 3.6 fixture units.
  • Half-bath group: toilet and sink, 2.6.
  • Kitchen group: sink and dishwasher, 2.5.
  • Laundry group: washer standpipe and laundry tub, 2.5.

A second sink in a full bath, a separate shower stall or a bar sink go in as single fixtures on top of the group. A hose bibb counts 2.5 on its own. The code's note says that value assumes about 2.5 gallons per minute, like a single lawn sprinkler, so a hose bibb that has to feed more needs a higher value.

The table also splits each value into hot and cold. The calculator shows both, because the hot side, which runs through the water heater, is sized on its own load.

From fixture units to gallons per minute

The pipe has to carry a flow, so the total is converted with IRC Table P2903.6(1). The conversion is not linear: 1 fixture unit is 3.0 gallons per minute, while 10 fixture units are only 14.6, because the more fixtures a house has, the smaller the share that runs at once.

The table has two columns. Houses almost always have tank toilets, so the calculator uses that column unless you pick flushometer valves, the tankless kind found in commercial restrooms. When your total falls between two rows, the calculator reads the next row up, so it never understates the flow. The residential table stops at 50 fixture units and 29.1 gallons per minute. Above that, the calculator tells you so instead of guessing.

A worked example

Take a house with 2 full bathrooms, 1 half bath, a kitchen with a dishwasher, a washer in the garage and 2 outdoor hose bibbs. The full baths count 3.6 each, the half bath 2.6, the kitchen group 2.5, the washer 1.4 and each hose bibb 2.5. The total is 18.7 fixture units, of which 6.4 on the hot side and 14.9 on the cold side.

Table P2903.6(1) has no row for 18.7, so the calculator moves up to the 19 fixture-unit row: a peak demand of 19.2 gallons per minute. That is the flow the water service has to deliver at the busiest moment of the day.

What comes next: sizing the pipe

The peak flow is the starting point, not the pipe size. Section P2903.7 of the code says the water service pipe may not be smaller than 3/4 inch, and that mains and risers are sized from three things together: the demand in gallons per minute, the water pressure available at the street or the well, and the friction loss through the meter and along the pipe, fittings included. A house far from the street with low pressure can need a larger pipe than the flow alone suggests.

IRC, IPC or UPC?

The values on this page are the International Residential Code's. Some states and cities adopt the Uniform Plumbing Code instead, and it weights fixtures differently: in the California Plumbing Code, which is based on the UPC, Table 610.3 gives a bathtub and a clothes washer noticeably higher values. Check which code your inspector enforces before you rely on a total.

Questions people ask

How many fixture units is a full bathroom?

3.6 water supply fixture units in IRC Table P2903.6, counting the toilet, the sink and a tub or shower stall as one group. Of those, 1.5 are on the hot side and 2.7 on the cold side.

Is a fixture unit the same as a gallon per minute?

No. Fixture units are a weighted count. The code converts the total into gallons per minute with Table P2903.6(1), and the conversion flattens out as the count grows: 10 fixture units are 14.6 gallons per minute, not ten times the flow of one.

Do outdoor faucets count?

Yes. Each hose bibb is 2.5 fixture units, all on the cold side. The code's value assumes about 2.5 gallons per minute; an irrigation connection that draws more should be counted with a higher value.

Why does my plumber's number differ from this one?

Usually because the town uses a different code. The Uniform Plumbing Code and some local amendments assign their own values, and an engineered design can use other methods altogether.