Peak Water Demand Calculator

Enter the total water supply fixture units of the house. The calculator reads the residential code's demand table and gives the peak flow, in gallons per minute, that the water service and the main lines have to carry.

Add them up with the fixture units calculator, or take them from your plumbing plan.

Homes almost always have tank toilets. Flushometer valves are the tankless kind found in commercial restrooms.

Peak demand

17.5 gpm

Load
15 w.s.f.u.
Table row used
15 w.s.f.u.
Toilets
Tank toilets

The row below (14 w.s.f.u.) gives 17 gpm. The calculator never reads down.

From IRC 2021 Table P2903.6(1). A planning check, not a stamped design.

Peak demand is the flow at the busiest moment, when several fixtures run together. For 21 fixture units in a house with tank toilets, IRC Table P2903.6(1) gives 21.5 gallons per minute, read from the 25 fixture-unit row.

Why demand is not the sum of every fixture

If every faucet, shower and toilet in a house ran at full flow at the same time, the pipe would need to be enormous. They never do. The code's demand table is built on the odds that fixtures overlap, so the flow grows much more slowly than the number of fixtures: 1 fixture unit is 3.0 gallons per minute, 10 fixture units are 14.6, and 50 fixture units, a big house, are 29.1.

That is also why you cannot add up the gallons per minute of each fixture. Add up the fixture units first, with the fixture units calculator or your plumbing plan, then convert the total once.

Tank toilets or flushometer valves

Table P2903.6(1) has two columns. Tank toilets refill slowly from a small supply, so houses use the tank column. Flushometer valves, the tankless toilets of office and school restrooms, draw a large flow for a few seconds, so their column starts at 5 fixture units and 15.0 gallons per minute and climbs much faster. Pick flushometer only if the building really has them.

Reading between the rows

The table lists whole loads one by one up to 20 and then jumps in steps of 5. When your total falls between two rows, the calculator reads the next row up, which never understates the flow. The code does not spell out a rule for loads between rows, so we chose the reading that errs toward a larger pipe. The result shows the row below as well, so you can see how much it matters.

The residential table stops at 50 fixture units. Above that, the calculator says so instead of guessing: larger buildings use the longer table in Appendix E of the International Plumbing Code or an engineered design.

A worked example

Say the fixture units of a house add up to 21. The table goes from the 20 row straight to the 25 row, so the calculator reads the 25 row: 21.5 gallons per minute. Reading down to the 20 row would give 19.6, a smaller flow that the next fixture could already exceed.

What the number is used for

Section P2903.7 of the code sizes the water service, the mains and the risers from three things together: this peak demand, the pressure available at the street or the well, and the friction loss through the meter and the pipe, fittings included. It also sets a floor: the water service may not be smaller than 3/4 inch. A long service from the street or a low-pressure well can push the size up even when the demand is modest.

Questions people ask

How many gallons per minute does a house need?

It depends on the fixtures. Count them in fixture units and convert the total with Table P2903.6(1): a modest house often lands somewhere between 10 and 20 fixture units, which the table puts at 14.6 to 19.6 gallons per minute with tank toilets.

Can I use this for a well pump?

The peak demand is a useful starting point for a well pump and pressure tank, but pump sizing also depends on the well's yield and the pressure switch settings. Ask the well contractor to confirm.

What if my total is above 50?

The residential table ends at 50 fixture units. Use Appendix E of the International Plumbing Code, which continues the table for larger buildings, or have the system designed by an engineer.