Gas Load Calculator: BTU to CFH

Enter the input rating of each gas appliance, from its rating plate. The calculator adds them up the way the fuel gas code does and turns the total into cubic feet per hour of natural gas, or into thousands of Btu per hour and gallons for propane.

The input rating on each appliance's rating plate. Leave a field empty if you do not have that appliance.

A grill, pool heater or generator, for example.

Your gas utility can tell you the local figure. 1,000 is the code's example value.

Optional, from your propane supplier. Only needed for a figure in cubic feet per hour.

Gas demand

207 cubic feet per hour

Appliances counted
4
Total input
207,000 Btu/h
Heating value used
1,000 Btu per cubic foot
At the U.S. average of 1,036
199.8 cubic feet per hour
Therms per hour at full input
2.07

To size the pipe, enter the total input, 207,000 Btu/h, in the gas pipe size calculator, which does this conversion for the code's natural gas tables.

The code counts every appliance at full input at the same time, unless a lower combined load can be established.

IFGC 2021 Section 402.2 and Appendix A, A102.1; EIA Btu conversion factors.

Gas pipe is sized for the total input of every appliance it serves. Appliances rated 80,000, 40,000, 65,000 and 22,000 Btu per hour add up to 207,000 Btu per hour, which at 1,000 Btu per cubic foot is 207 cubic feet of natural gas per hour.

How the code adds up the load

Section 402.2 of the International Fuel Gas Code sets the gas demand as the sum of the maximum input of every appliance the piping serves. It sizes the pipe as if all of them could run at full input at the same time; a lower combined load is allowed only where a diversity of load can be established. The code's appendix asks for the input rating given by the appliance maker whenever possible: it is printed on the rating plate, in Btu per hour.

From Btu to cubic feet

To turn the total into cubic feet per hour, divide it by the heating value of the gas, in Btu per cubic foot. The code tells you to get the local average from your gas supplier. Its worked examples use 1,000 Btu per cubic foot, and the U.S. Energy Information Administration puts the 2026 average for gas delivered to consumers at 1,036. The richer the gas, the fewer cubic feet carry the same load.

If your bill is in therms: a therm is 100,000 Btu, so the calculator also shows how many therms an hour the appliances burn at full input.

A worked example

A house has a furnace rated 80,000 Btu per hour, a water heater rated 40,000, a range rated 65,000 and a dryer rated 22,000. Together they come to 207,000 Btu per hour. At the code's example heating value of 1,000 Btu per cubic foot, that is 207 cubic feet per hour; at the U.S. average of 1,036 it would be 199.8. At full input the four appliances burn 2.07 therms an hour.

Propane

The code's propane pipe tables list capacity in thousands of Btu per hour, not cubic feet, so for sizing you only need the total input: the pipe size calculator takes it in Btu per hour for both gases. To estimate how fast a tank empties, the EIA's figure of 91,452 Btu per gallon of propane turns the load into gallons per hour at full input. A figure in cubic feet per hour needs the heat content of your propane, which your supplier can give.

Next: the pipe size

Enter the total input, in Btu per hour, in the gas pipe size calculator: it converts it for the natural gas tables, reads the code tables for the length of your longest run and gives the pipe size.

Questions people ask

How many CFH is 100,000 BTU?

At 1,000 Btu per cubic foot, 100 cubic feet per hour. At the U.S. average of 1,036 Btu per cubic foot, about 96.5. Ask your gas supplier for the local figure.

How do I convert BTU to CFH for propane?

Divide by the heat content of your propane per cubic foot, which your supplier can give you. For pipe sizing you can skip the step: the code's propane tables read capacity in thousands of Btu per hour, and the pipe size calculator takes the total input in Btu per hour.

Do I have to count every gas appliance?

Yes. Section 402.2 sizes the pipe for all the appliances it serves at full input at the same time, unless a lower combined load can be established. Count the ones you plan to add, too.