Gas Pipe Size Calculator

Enter the total input of the appliances on the line and the length of the longest run. The calculator reads the same capacity table an inspector would use and gives you the smallest black iron pipe that can carry the load.

Low-pressure systems: natural gas under 2 psi, propane after the second-stage regulator.

Add up the input ratings on every appliance’s rating plate.

Pipe length from the meter or regulator to the farthest appliance, plus the fitting allowance.

Natural gas only. Your utility can tell you the local figure; 1,000 is the code’s example value.

Smallest Schedule 40 pipe that carries the load

1 in.

Demand
200 CFH
Capacity of 1 in. at 40 ft
320 CFH
Table row used
40 ft

One size smaller (3/4 in.) carries only 170 CFH at this length.

Capacity at 40 ft for each size. The first bar past the dashed line is the size.

From IFGC 2021 Table 402.4(2). A planning check, not a stamped design.

Gas pipe is sized by two numbers together: the total load of the appliances it feeds and the length of pipe to the farthest one. With 207,000 Btu/h on natural gas and a 46 ft run, the 2021 IFGC table points to 1 in. Schedule 40 pipe.

How the sizing works

Gas reaches your appliances at very low pressure. The table this calculator uses assumes the pipe network loses no more than half an inch of water column (0.5 in. w.c.) between the meter and the farthest burner. The code also has a stricter 0.3 in. w.c. table, which gives smaller capacities. Every foot of pipe eats a little of that budget through friction, so a pipe that easily feeds a furnace ten feet from the meter can starve the same furnace at the far end of the house.

That is why the code tables are organized by length. Each row is a pipe length, each column a pipe size, and each cell the most gas that size can carry over that length without losing more than the allowed pressure. Natural gas capacities are in cubic feet per hour (CFH). Propane capacities are already in thousands of Btu per hour, because propane carries about two and a half times the energy per cubic foot.

The calculator follows the longest length method in IFGC Section 402.4.1:

  1. Add up the maximum input of every appliance on the system, as Section 402.2 requires. The rating plate on each appliance gives it in Btu/h.
  2. For natural gas, divide by the heating value of your gas to get CFH. The code's worked examples use 1,000 Btu per cubic foot; your utility can give you the local number.
  3. Find the row for the longest run. If your length falls between two rows, the code's appendix says to use the next longer row.
  4. Read across to the first size whose capacity covers the demand.

Measuring the longest run

The run that matters is the pipe length from the point of delivery to the most remote outlet. On natural gas, the code defines the point of delivery as the outlet of the service meter assembly. On propane, it is the outlet of the service pressure regulator, and the low-pressure table on this page covers the pipe from the single-stage or second-stage regulator to the appliances. Measure along the path the pipe actually takes, up walls and across joists, not in a straight line across the floor plan.

Fittings add resistance too. The code's appendix says that a run with four or more fittings should get an allowance in equivalent length of pipe, using Table A102.2: each elbow, tee and valve counts as a few extra feet of straight pipe. Add those feet to your measured run before you look up the row. Enter the total, not the tape-measure length, in the calculator above.

The answer this calculator gives is the size of the first section out of the meter or regulator, the one that carries the whole load. On a branched system, each later section is sized the same way: the same longest length, but only the load that section carries. That is how a system can start at a large size and step down near the appliances.

A worked example

Say a house on natural gas has a furnace rated at 80,000 Btu/h, a tank water heater at 40,000 Btu/h, a range at 65,000 Btu/h and a dryer at 22,000 Btu/h. The total connected load is 207,000 Btu/h. At the code's example heating value of 1,000 Btu per cubic foot, that is a demand of 207 CFH.

The farthest appliance is the range, 46 ft of pipe from the meter. There is no 46 ft row in the table, so you move up to the 50 ft row. In that row, 3/4 in. pipe carries 151 CFH, which is not enough. The next size, 1 in., carries 284 CFH. So the first section out of the meter should be 1 in. Schedule 40 pipe.

The natural gas table

These are the capacities the calculator uses for natural gas, for pipe sizes up to 2 in. and runs up to 200 ft. The full code table goes further in both directions.

IFGC 2021 Table 402.4(2): Schedule 40 metallic pipe, natural gas, inlet Less than 2 psi, pressure drop 0.5 in. w.c., specific gravity 0.6. Capacity in cubic feet of gas per hour (CFH).
Length (ft)1/2 in.3/4 in.1 in.1-1/4 in.1-1/2 in.2 in.
101723606781,3902,0904,020
201182474669571,4302,760
30951993747681,1502,220
40811703206579851,900
50721512845838731,680
60651372575287911,520
70601262374867281,400
80561172204526771,300
90521102074246351,220
100501041954006001,160
12544921733555321,020
1504083157322482928
1753777144296443854
2003471134275412794

The propane table

For propane on the low-pressure side of the regulator, the code uses a separate table based on an 11.0 in. w.c. supply and a 0.5 in. w.c. drop. Never size a propane line by converting the load to cubic feet and reading the natural gas table: the gases flow differently, and the answer would be wrong.

IFGC 2021 Table 402.4(28): Schedule 40 metallic pipe, undiluted propane, inlet 11.0 in. w.c., pressure drop 0.5 in. w.c., specific gravity 1.5. Capacity in thousands of Btu per hour (kBtu/h).
Length (ft)1/2 in.3/4 in.1 in.1-1/4 in.1-1/2 in.2 in.
102916081,1502,3503,5206,790
202004187871,6202,4204,660
301603366321,3001,9403,750
401372875411,1101,6603,210
501222554809851,4802,840
601102314348921,3402,570
701012124008211,2302,370
80941973727631,1402,200
90891853497161,0702,070
100841753306771,0101,950
125741552926008991,730
150671402655438141,570
175621292435007491,440
200581202274656971,340

When this table is not the right one

  • Flexible yellow tubing (CSST). Corrugated stainless steel tubing has its own tables, and each manufacturer publishes sizing charts for its product. Size CSST from those charts, not from black iron numbers.
  • Copper and plastic pipe. The code has separate tables for semi-rigid tubing and for polyethylene plastic pipe and tubing.
  • Elevated pressure systems. Some newer homes run natural gas at 2 psi to a regulator near the appliances. Those systems use different tables and a different pressure drop.
  • The high-pressure side of a propane system. Between the tank and the second-stage regulator, the pressure is measured in psi and the tables are different again.
  • Specific gravity above 0.70. The code allows natural gas tables to be used directly only for gas with a specific gravity of 0.70 or less.

Questions people ask

Can I just use the pipe size of the old line?

Only if the load has not grown. Adding a range, a tankless water heater or a generator is exactly when an old line ends up too small, and an undersized line shows up as lazy flames, sooting or appliances that shut down on low pressure. Re-run the numbers with the new total.

Do I measure from the meter or from the tank?

On natural gas, measure from the outlet of the meter. On propane, the code puts the point of delivery at the outlet of the service pressure regulator, and the low-pressure table covers the pipe after the single-stage or second-stage regulator, not from the tank itself.

Why does a tankless water heater change the pipe size so much?

Because pipe is sized on the maximum input of every appliance running at once, and a whole-house tankless unit can draw several times what a tank heater does. Check its rating plate and add it to the total before you size anything.

Is the answer the same in every state?

Most US jurisdictions adopt either the International Fuel Gas Code or NFPA 54, the National Fuel Gas Code. Editions and local amendments differ, so check which one your inspector enforces before you buy pipe.