Choose what you are spacing: a connector from a wood, coal, oil or gas appliance, or an appliance with a clearance on its label. The calculator gives the clearance to combustible material in the 2021 International Residential Code and, if you add protection to the wall or ceiling, the reduced clearance of Table M1306.2, or of Table G2409.2 for gas.
Clearance to combustibles
18 in.
- Required with no protection
- 18 in. (Table M1803.3.4)
The note to Table M1803.3.4: its clearances apply to unlisted single-wall chimney and vent connectors. A listed connector follows its listing.
2021 IRC Table M1803.3.4.
An unlisted single-wall stovepipe from a wood stove needs 18 inches to unprotected combustible material. With 24 gage steel on a 1-inch ventilated airspace on the wall, Table M1306.2 lists 6 inches, and the calculator keeps 12 because of the code's limit for solid-fuel appliances.
Connectors for wood, coal and oil
A connector is the pipe between an appliance and its chimney or vent. Table M1803.3.4 sets its clearance to combustible material:
| Connector | Oil or solid fuel | Oil, listed for Type L |
|---|---|---|
| Single-wall metal pipe | 18 | 9 |
| Type L vent piping | 9 | 3 |
The table applies to unlisted single-wall chimney and vent connectors; where listed Type L vent piping is used, its listing sets the clearance. A listed connector, such as a listed double-wall stovepipe, follows its listing and the manufacturer's instructions.
Gas vent connectors
For gas appliances the clearances are in Table G2427.10.5 of the fuel gas chapter, in inches. They apply unless the installation instructions of a listed appliance or connector give different clearances, in which case the listed ones apply. An exception allows a smaller clearance where the combustible material is protected as Table G2409.2 specifies for vent connectors.
| Appliance | Type B | Type L | Single wall | Factory chimney |
|---|---|---|---|---|
| Listed with a draft hood, or for Type B vents | Listed | Listed | 6 | Listed |
| Boiler or furnace, listed conversion burner, draft hood | 6 | 6 | 9 | Listed |
| Listed for Type L vents | No | Listed | 9 | Listed |
| Listed gas-fired toilet | No | Listed | Listed | Listed |
| Unlisted, with a draft hood | No | 6 | 9 | Listed |
| Other residential and low-heat | No | 9 | 18 | Listed |
| Medium-heat appliance | No | No | 36 | Listed |
Appliances
Section M1306.1 sends you to the appliance itself: it is installed with the clearances from unprotected combustible material shown on its label and in the manufacturer's installation instructions. For an appliance, enter the label's clearance for the side you are checking.
Reducing the clearance with protection
Table M1306.2 allows a smaller clearance where the combustible surface is covered with one of eight forms of protection, over all of it that lies within the unprotected clearance. For gas appliances and their vent connectors the fuel gas chapter has its own Table G2409.2, with the same eight forms and the same numbers. Both chapters also accept a reduced-clearance protective assembly listed and labeled to UL 1618. Column 1 is for clearances above an appliance or a horizontal connector; column 2 for the sides and rear of an appliance, vertical connectors and single-wall metal pipe.
| Protection | 36 | 18 | 12 | 9 | 6 |
|---|---|---|---|---|---|
| 3-1/2 in. masonry, no airspace | 24 | 12 | 9 | 6 | 5 |
| 1/2 in. insulation board over 1 in. batts | 18 | 9 | 6 | 5 | 3 |
| 24 ga steel over 1 in. batts, ventilated | 12 | 6 | 4 | 3 | 3 |
| 3-1/2 in. masonry, ventilated airspace | 12 | 6 | 6 | 6 | 6 |
| 24 ga steel, 1 in. ventilated airspace | 12 | 6 | 4 | 3 | 2 |
| 1/2 in. insulation board, ventilated | 12 | 6 | 4 | 3 | 3 |
| 24 ga steel over 24 ga steel, ventilated | 12 | 6 | 4 | 3 | 3 |
| 1 in. batts between two 24 ga steel sheets, ventilated | 12 | 6 | 4 | 3 | 3 |
| Protection | 36 | 18 | 12 | 9 | 6 |
|---|---|---|---|---|---|
| 3-1/2 in. masonry, no airspace | — | — | — | — | — |
| 1/2 in. insulation board over 1 in. batts | 24 | 12 | 9 | 6 | 4 |
| 24 ga steel over 1 in. batts, ventilated | 18 | 9 | 6 | 5 | 3 |
| 3-1/2 in. masonry, ventilated airspace | — | — | — | — | — |
| 24 ga steel, 1 in. ventilated airspace | 18 | 9 | 6 | 5 | 3 |
| 1/2 in. insulation board, ventilated | 18 | 9 | 6 | 5 | 3 |
| 24 ga steel over 24 ga steel, ventilated | 18 | 9 | 6 | 5 | 3 |
| 1 in. batts between two 24 ga steel sheets, ventilated | 18 | 9 | 6 | 5 | 3 |
The notes and Section M1306.2.2 add conditions: a ventilated protector stands at least 1 inch off the combustible wall, with its edges open at least 1 inch for air; spacers and ties are noncombustible and are not placed directly opposite the appliance or connector; there is at least 1 inch between the appliance and the protector; mineral wool and glass fiber batts have a density of at least 8 pounds per cubic foot and a melting point of at least 1,500 °F; and the reduction must not interfere with combustion air, draft hood relief or access for service.
The tables have columns for 36, 18, 12, 9 and 6 inches. For gas, Section G2409.2 requires straight-line interpolation for a clearance between two columns and forbids extrapolation below the table, and it allows no reduction where the appliance's listing prohibits one; central furnaces, low-pressure boilers and air-conditioning appliances may use it only where the manufacturer's instructions allow. Section M1306.2 says nothing about values between columns, so for other fuels the calculator reads the next larger column, which gives the larger reduced clearance. Over 36 or under 6 inches it does not reduce the clearance.
The 12-inch limit for wood and coal
Section M1306.2.3 does not let the table reduce the clearance of a solid-fuel appliance listed for 12 inches or less, and for one listed for more than 12 inches it does not let the table go below 12 inches. The section speaks of appliances and does not say whether the limit reaches their connectors. The calculator takes the cautious reading and applies it to wood and coal connectors too. The limit does not apply to oil or gas.
A worked example
A wood stove's unlisted single-wall stovepipe runs up beside a wall with wood framing.
- Table M1803.3.4: 18 inches to unprotected combustibles.
- With 24 gage galvanized steel on a 1-inch ventilated airspace, the 18-inch column of Table M1306.2, sides and rear, lists 6 inches.
- Because the stove burns wood, the calculator keeps 12 inches, the 12-inch limit of Section M1306.2.3.
The steel has to cover the wall over the whole area within 18 inches of the pipe.
Masonry and factory-built chimneys
The chimney itself has its own clearances: the airspace around a masonry chimney is on our hearth extension and chimney height calculator, and a factory-built chimney is installed to its listing and the manufacturer's instructions.
Questions people ask
How far does a stovepipe have to be from a wall?
An unlisted single-wall stovepipe from a wood, coal or oil appliance needs 18 inches to unprotected combustible material (Table M1803.3.4). A listed connector follows its listing.
How close can a wood stove be to a wall with a heat shield?
It depends on the clearance on the stove's label. A stove listed for 36 inches at the sides, with 24 gage steel on a 1-inch ventilated airspace, can come to 12 inches under Table M1306.2. Section M1306.2.3 never lets the table take a wood stove below 12 inches.
What clearance does a gas water heater vent connector need?
For a listed appliance with a draft hood, single-wall metal pipe needs 6 inches to combustibles; a listed Type B gas vent connector follows its listing (Table G2427.10.5).
Does double-wall stovepipe need less clearance?
The code's 18 inches is for unlisted single-wall connectors. A listed double-wall connector is installed to the clearance in its listing and instructions, which is where any smaller figure comes from.
Sources
- 2021 International Residential Code, Chapter 18: Chimneys and Vents (UpCodes, Colorado DFPC Residential Code 2021) — Section M1803.3.4 and Table M1803.3.4
- 2021 International Residential Code, Chapter 13: General Mechanical System Requirements (UpCodes, Colorado DFPC) — Section M1306, Table M1306.2 and its notes
- 2021 International Residential Code, Chapter 24: Fuel Gas (UpCodes, Colorado DFPC) — Section G2427.10.5, Table G2427.10.5, Section G2409 and Table G2409.2
- 2021 International Residential Code, Chapters 13, 18 and 24 (UpCodes, New Jersey edition) — used to check the three tables