Heating, Cooling & Energy · Calculator
Attic Insulation Calculator
Choose your climate zone and how much insulation the attic has now. The calculator gives the R-value ENERGY STAR suggests adding and, from the blown insulation's coverage chart, the thickness and the number of bags for your attic.
Insulation to add to the attic
R60
- Zone
- Zones 4A and 4B
- Floor insulation
- R19
- Thickness to add
- at least 20.5 in
- Bags for 1,000 sq ft
- 32 (31.5 per 1,000 sq ft)
Owens Corning gives the stated R-value for the minimum number of bags per 1,000 sq ft at the specified thickness: both count.
Keep insulation away from recessed lights not rated for contact with it, and from flues and chimneys, as the maker's instructions say.
ENERGY STAR recommended home insulation R-values; Owens Corning AttiCat coverage chart (2022).
ENERGY STAR suggests adding R60 of insulation to an uninsulated attic in Zones 4A and 4B. With AttiCat blown fiberglass, that is at least 20.5 inches, about 32 bags for 1,000 square feet.
How much to add
ENERGY STAR publishes the insulation levels it considers cost-effective when you upgrade an existing wood-framed house, based on Table R402.1.3 of the 2021 International Energy Conservation Code. For the attic, it gives the R-value to add, depending on whether the attic has no insulation or already has 3 to 4 inches:
| Zone | None | 3–4 in | Floor |
|---|---|---|---|
| 1 | R30 | R25 | R13 |
| 2 | R49 | R38 | R13 |
| 3 | R49 | R38 | R19 |
| 4A and 4B | R60 | R49 | R19 |
| 4C, 5 and 6 | R60 | R49 | R30 |
| 7 and 8 | R60 | R49 | R38 |
The table covers these two cases only. The floor column is the insulation ENERGY STAR suggests for floors.
From R-value to inches and bags
Owens Corning gives the stated R-value of its AttiCat blown fiberglass for a minimum number of bags per 1,000 square feet at a specified thickness, so both count. Its chart lists at least 13.5 inches and 19 bags per 1,000 square feet for R-38, 17 inches and 25 bags for R-49, and 20.5 inches and 31.5 bags for R-60. For another product, choose Another product and enter the figures from its maker's coverage chart.
A worked example
A house in climate zone 4A has an uninsulated attic of 1,000 square feet. ENERGY STAR suggests adding R60. On the AttiCat chart, R-60 takes at least 20.5 inches and 31.5 bags per 1,000 square feet, so 32 bags for this attic.
Before you blow it in
Owens Corning's instructions warn not to insulate on top of or within 3 inches of recessed light fixtures and similar devices unless they are approved to be covered, and not to place insulation in the air spaces around metal flues, chimneys or fireplaces. The residential code also asks that insulation not block the air at eave vents; see the attic ventilation calculator.
Questions people ask
How much attic insulation do I need?
ENERGY STAR suggests adding R30 to R60 to an uninsulated attic, depending on the climate zone: R30 in zone 1, R49 in zones 2 and 3 and R60 in zones 4 to 8.
How many inches is R-38, R-49 or R-60?
It depends on the product. For Owens Corning AttiCat blown fiberglass, at least 13.5 inches for R-38, 17 for R-49 and 20.5 for R-60. Other products list their own figures on the bag.
I already have some insulation. How much do I add?
If the attic has 3 to 4 inches, ENERGY STAR suggests adding R25 in zone 1, R38 in zones 2 and 3 and R49 in zones 4 to 8.
Sources
- ENERGY STAR: Recommended Home Insulation R-Values — insulation to add to attics and floors by climate zone, based on the 2021 IECC
- Owens Corning AttiCat Expanding Blown-in PINK FIBERGLAS Insulation, application instructions (Pub. No. 10009393-E, November 2022) — coverage chart: bags per 1,000 sq ft and minimum thickness by R-value