Roof & Exterior · Calculator
Attic Ventilation Calculator
Enter the area of the attic and choose the rule that applies. The calculator gives the net free ventilating area the code asks for, how it splits between upper and lower vents and, from the vents' rated area, how many of each to install.
Ventilation needed
1,440 sq in
- Net free area
- 10 sq ft = 1,440 sq in (1/150)
- Upper vents, 50%
- 720 sq in
- Lower vents
- 720 sq in
Keep at least 1 in of space between the insulation and the roof sheathing at the vents.
2021 IRC (Seattle edition), Sections R806.1 to R806.3.
The code asks for 1 square foot of net free vent area for every 150 square feet of attic. A 1,500 square foot attic needs 10 square feet, or 1,440 square inches.
The rule and its exception
Section R806.2 of the residential code sets the minimum net free ventilating area at 1/150 of the area of the vented space. It drops to 1/300 only when both of these conditions are met:
- in Climate Zones 6, 7 and 8, a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling;
- at least 40 and not more than 50 percent of the required area is in vents in the upper part of the attic, not more than 3 feet below the ridge, and the rest in the bottom third of the attic.
Net free area
The code counts net free ventilating area, in square inches for vents. Use the net free area the vent's label or the maker's literature gives. Section R806.1 also limits the openings to between 1/16 and 1/4 inch, or asks for a screen with openings of that size, to keep out rain, snow, birds and rodents.
A worked example
An attic over a 1,500 square foot ceiling is ventilated under the general rule: 1,500 ÷ 150 = 10 square feet of net free area, which is 10 × 144 = 1,440 square inches. Split evenly, that is 720 square inches in the upper vents and 720 in the soffit vents. Under the 1/300 exception the same attic would need half as much.
Keep the air moving
Where there are eave or soffit vents, Section R806.3 forbids blocking, bridging or insulation that stops the air, and asks for at least 1 inch of space between the insulation and the roof sheathing at the vent.
Unvented attics
Section R806.5 also allows unvented attics, with the insulation at the roof deck and a list of conditions. This calculator is for vented attics only.
Questions people ask
How much attic ventilation do I need?
Under Section R806.2, 1 square foot of net free area for every 150 square feet of attic: 10 square feet, or 1,440 square inches, for a 1,500 square foot attic. With both conditions of the 1/300 exception, 720 square inches.
Do intake and exhaust vents have to be equal?
The 1/300 exception asks for 40 to 50 percent of the area in upper vents and the rest in the bottom third of the attic. Under the general 1/150 rule, Section R806.2 sets no split.
Where do the upper vents go?
Under the 1/300 exception, not more than 3 feet below the ridge or the highest point of the space, measured vertically, with the rest of the vents in the bottom third of the attic. Under the general 1/150 rule, Section R806.2 does not say where.
Sources
- 2021 Seattle Residential Code, Chapter 8: Roof-Ceiling Construction — the city's edition of the 2021 International Residential Code; Section R806, roof ventilation