Chimney Draft Calculator
Enter the height of the chimney, the outdoor temperature, the average temperature of the gases inside it and the elevation of the house. The calculator gives the theoretical draft in inches of water and pascals, using the equation in the ASHRAE Handbook.
Theoretical chimney draft
0.111 in. of water
- Temperature difference
- 270 °F
- Air pressure at your elevation
- 29.92 in. of mercury
- Theoretical draft
- 0.111 in. of water
- In pascals
- 27.6 Pa
This is the most the chimney can pull. Friction in the flue, bends and a house under negative pressure all take some away, so a gauge reads less.
For comparison: Drolet asks for 0.05 to 0.07 in. of water measured at a medium-high fire, and warns that under 0.03 the stove is hard to run and over 0.1 it over-fires. Woodstock gives 0.04 to 0.07 in. measured with no fire in the stove. Your stove's manual has its own figure.
ASHRAE Handbook, HVAC Systems and Equipment 2024, Chapter 35, Equation 9; NOAA pressure altitude; makers' manuals.
A 20 foot chimney carrying gases at an average of 300 °F on a 30 °F day at sea level has a theoretical draft of 0.111 inches of water, about 27.6 pascals. A gauge reads less, because the flue's own friction takes part of it.
Where draft comes from
Hot gas is lighter than cold air. The column of hot gas inside a chimney weighs less than a column of outdoor air of the same height, and the difference pulls air into the fire and pushes smoke out of the top. Natural Resources Canada puts it simply: the hotter the gas compared with the outdoor air, the stronger the draft. The ASHRAE Handbook adds the other lever: theoretical draft grows in direct proportion to the height of the chimney.
The formula
The calculator uses Equation 9 of Chapter 35 of the ASHRAE Handbook, HVAC Systems and Equipment (2024):
Draft = 0.2554 × B × H × (1/To − 1/Tm)
- Draft is in inches of water.
- B is the local air pressure in inches of mercury. The calculator works it out from the elevation with the National Weather Service's pressure-altitude equation.
- H is the height of the chimney in feet.
- To is the outdoor temperature and Tm the average temperature of the gases in the chimney, both in degrees Rankine: degrees Fahrenheit plus 459.67.
One inch of water is 249.0889 pascals. As a check, the same chapter's Table 6 gives about 0.2, 0.4, 0.5 and 0.7 inches of water per 100 feet of chimney for gases 100, 200, 300 and 500 °F warmer than 60 °F air at sea level, and the calculator matches it.
Theoretical is not what a gauge reads
The equation gives the most the chimney can pull. ASHRAE subtracts from it the friction of the gases moving through the flue and any negative pressure in the house to get the draft actually available at the appliance. The average gas temperature also matters: gases cool as they rise, so the average over the whole chimney is lower than the temperature on a stovepipe thermometer.
What stove makers ask for
| Maker | Draft | Measured |
|---|---|---|
| Drolet (Nordic and Sawman stoves) | 0.05 to 0.07 in. of water; under 0.03 the stove is hard to run, over 0.10 it over-fires | with a pressure gauge, at a medium-high fire |
| Woodstock Soapstone (Progress Hybrid) | 10 to 18 pascals, 0.04 to 0.07 in. of water | with no fire in the stove |
The two makers measure in different conditions, so the figures are not one range. Your appliance's manual has the figure that applies to it. For open fireplaces ASHRAE uses another test: air entering the fireplace opening at an average of at least 0.8 feet per second, with flue gases 300 to 500 °F warmer than the outdoor air, should keep smoke out of the room.
What weakens draft
- A cold chimney. A chimney on an outside wall is chilled by the outdoor air, which reduces the draft at the appliance. With no fire, the air inside cools to the outdoor temperature and the chimney gives no draft at all, which is why a cold fireplace can smoke when it is first lit.
- A house under negative pressure. Exhaust fans lower the pressure indoors, and that works against the chimney: smoke can spill into the room. England's Approved Document J advises against extract fans in the same room as a solid-fuel appliance.
- A short chimney. The Canadian guide says the total system height, from the floor the appliance stands on to the top of the chimney, should never be less than 15 feet (4.6 meters). England's guidance treats 4.5 meters as a minimum that can work if its other rules are followed.
- Wind and surroundings. Approved Document J names wind exposure, tall buildings, high trees and high ground nearby as things that can upset draft. How far the chimney must rise above the roof is a separate code rule: see the hearth extension and chimney height calculator.
Too much draft is a problem too: the Canadian guide notes that chimneys taller than about 25 feet (8 meters) sometimes pull more than the appliance needs.
Questions people ask
What is a good draft for a wood stove?
It depends on the stove, so check its manual. Drolet asks for 0.05 to 0.07 inches of water at a medium-high fire and says under 0.03 causes trouble and over 0.10 over-fires the stove. Woodstock Soapstone gives 0.04 to 0.07 inches measured with no fire.
Does a taller chimney draw better?
Yes. Theoretical draft grows in proportion to height: a chimney twice as tall pulls twice as hard with the same temperatures. The Canadian wood-heating guide sets 15 feet as the minimum total system height.
Why does my fireplace smoke when I light it?
A cold chimney has no draft until it warms up, and a house under negative pressure, from exhaust fans for example, pulls against it. The Canadian wood-heating guide notes that opening a window or door nearby while the fire is lit gets it started, but only masks the problem: the fix is in the installation.
Does altitude affect chimney draft?
Yes. Draft is proportional to the air pressure, which falls with altitude: at 5,000 feet it is about 17 percent lower than at sea level, and so is the draft. ASHRAE says compensation is usually needed above 2,000 feet.
Sources
- ASHRAE Handbook, HVAC Systems and Equipment 2024, Chapter 35: Chimney, Vent, and Fireplace Systems — Section 4, Equations 1 and 9 and Table 6; Section 9 on fireplaces
- NOAA National Weather Service: Pressure Altitude — equation between station pressure and altitude
- NIST Guide to the SI (SP 811), Appendix B.9 — inch of mercury 3,386.389 Pa, inch of water 249.0889 Pa
- Canada Mortgage and Housing Corporation and Natural Resources Canada: A Guide to Residential Wood Heating (2008) — chimney draft, cold chimneys, house depressurization, system height
- Approved Document J: Combustion appliances and fuel storage systems (England, 2010 edition with 2022 amendments) — paragraphs 1.20, 2.8 and 2.11
- Drolet: Nordic and Sawman wood stoves owner's manual (45030A) — draft section, page 21
- Woodstock Soapstone: Progress Hybrid 209b owner's manual (11-2025) — Smoke and the Chimney, page 30