Sill & Rafter

Electrical · Calculator

Breaker Size for Continuous Loads: the 125 Percent Rule

Enter the continuous and noncontinuous load in amperes, the conductor metal and the temperature column your equipment allows. The calculator applies the National Electrical Code: 125 percent of the continuous load, the next standard breaker size and the smallest conductor that both carries the load and is protected by that breaker.

Current expected to run for 3 hours or more: an EV charger, a water heater, baseboard heat, lighting left on all evening.

Only an assembly listed for 100 percent operation drops the 125 percent factor.

Use 75 °C only if the breaker and the equipment at the other end are both marked for it.

Breaker size

20 A

Load to size for
0 + 1.25 × 16 = 20 A
Smallest conductor
12 AWG copper
Its ampacity at 60 °C
20 A
Continuous load this breaker can carry
16 A

No correction for a hot attic, more than three current-carrying conductors together, or long runs: those can call for a larger conductor.

Some wiring methods and equipment set their own limits. Air conditioners and heat pumps follow the breaker size on their nameplate (Article 440). Your inspector's code edition decides.

NEC 2014: 210.19(A)(1), 210.20(A), 240.4, 240.6(A), Table 310.15(B)(16).

A 16 amp continuous load must be treated as 20 amps, so it needs a 20 amp breaker and at least 12 AWG copper wire at the 60 °C rating.

What a continuous load is

The code defines a continuous load as one whose maximum current is expected to continue for 3 hours or more. Some loads are continuous by rule: a storage water heater of 120 gallons or less is treated as one when its branch circuit is sized (Section 422.13).

The 125 percent rule

Sections 210.19(A)(1) and 210.20(A) say the same thing for the wire and for the breaker of a branch circuit: neither may be rated less than the noncontinuous load plus 125 percent of the continuous load. Sections 215.2(A)(1) and 215.3 repeat it for feeders. The only way out is an assembly, breaker and enclosure together, listed for operation at 100 percent of its rating, which is rare in homes.

Turned around, a breaker can carry a continuous load of 80 percent of its rating, since 100 ÷ 1.25 = 80: a 20 amp breaker, 16 amps. A separate rule, Section 210.23(A)(1), limits one piece of plug-in equipment to 80 percent of the branch circuit's rating.

Standard breaker sizes

The result is rounded up to a standard rating from Section 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 and 250 amps, and larger sizes above that.

Choosing the wire

The wire's ampacity comes from Table 310.15(B)(16), for no more than three current-carrying conductors in a raceway or cable at an ambient temperature of 30 °C. Section 110.14(C)(1) makes circuits of 100 amps or less, and wires from 14 to 1 AWG, use the 60 °C column unless the equipment is listed and identified for higher-rated conductors.

SizeCu 60 °CCu 75 °CAl 60 °CAl 75 °C
14 AWG1520——
12 AWG20251520
10 AWG30352530
8 AWG40503540
6 AWG55654050
4 AWG70855565
3 AWG851006575
2 AWG951157590
1 AWG11013085100

Small conductors have their own ceiling in Section 240.4(D), whatever the table says: 15 amps for 14 AWG copper, 20 for 12 AWG copper, 30 for 10 AWG copper, 15 for 12 AWG aluminum and 25 for 10 AWG aluminum. Where a wire's ampacity is not itself a standard breaker size, Section 240.4(B) lets the next standard size protect it, up to 800 amps, except on a branch circuit with more than one receptacle for plug-in loads.

When other rules apply

Air conditioners and heat pumps follow Article 440: their breaker may be up to 175 percent of the compressor's rated-load current, or 225 percent if it will not start, and the nameplate gives the maximum. Motors follow Article 430, worked out in our motor full-load current calculator. Hot attics, many conductors bundled together and long runs can each call for a larger wire than the table alone.

Questions people ask

What size breaker for a 16 amp continuous load?

A 20 amp breaker: 16 × 1.25 = 20.

Why can a 20 amp breaker only carry 16 amps continuously?

Because the code sizes breakers for continuous loads at 125 percent of the load, which leaves 80 percent of the rating, 16 amps, for a load that runs 3 hours or more.

Is a water heater a continuous load?

Yes. A storage water heater of 120 gallons or less is treated as a continuous load, so its circuit is sized at 125 percent of its marked rating.

What size wire goes on a 30 amp breaker?

At least 10 AWG copper: Section 240.4(D) limits 10 AWG copper to 30 amps, and 12 AWG copper to 20.

Sources