Electrical · Calculator
Motor Full-Load Current Calculator
Choose single- or three-phase, the horsepower and the rated voltage. The calculator looks up the full-load current in the National Electrical Code's tables and works out the minimum ampacity of the branch-circuit wire and the largest breaker or fuse the code allows for it.
Full-load current
8 A
- Wire ampacity, at least (125%)
- 10 A
- Breaker, at most (250%)
- 20 A
- Time-delay fuse, at most (175%)
- 15 A (from 14)
- Nontime-delay fuse, at most (300%)
- 25 A (from 24)
Use this table current, not the nameplate, to size the conductors and the breaker or fuse. Size the overload protection from the nameplate current instead.
The breaker and fuse figures are maximums; the next standard size above them is allowed when the figure is not a standard size.
NEC 2014: 430.6(A), 430.22, Tables 430.248, 430.250 and 430.52.
A 1 horsepower single-phase motor at 230 volts has a full-load current of 8 amps in the code's table. Its branch-circuit wire needs at least 10 amps of ampacity, and an inverse time breaker of up to 20 amps protects it.
Table current, not the nameplate
Section 430.6(A)(1) says to use the table values, not the current on the motor's nameplate, when sizing the conductors and the short-circuit and ground-fault protection of a general-purpose motor. The nameplate current is used for the overload protection, under Section 430.6(A)(2). The tables are typical values for motors at usual belted speeds with normal torque.
Single-phase motors (Table 430.248), amperes
| hp | 115 V | 200 V | 208 V | 230 V |
|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 | 7.2 | 4.1 | 4 | 3.6 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8 |
| 1-1/2 | 20 | 11.5 | 11 | 10 |
| 2 | 24 | 13.8 | 13.2 | 12 |
| 3 | 34 | 19.6 | 18.7 | 17 |
| 5 | 56 | 32.2 | 30.8 | 28 |
| 7-1/2 | 80 | 46 | 44 | 40 |
| 10 | 100 | 57.5 | 55 | 50 |
Three-phase motors (Table 430.250), amperes
| hp | 208 V | 230 V | 460 V |
|---|---|---|---|
| 1/2 | 2.4 | 2.2 | 1.1 |
| 3/4 | 3.5 | 3.2 | 1.6 |
| 1 | 4.6 | 4.2 | 2.1 |
| 1-1/2 | 6.6 | 6 | 3 |
| 2 | 7.5 | 6.8 | 3.4 |
| 3 | 10.6 | 9.6 | 4.8 |
| 5 | 16.7 | 15.2 | 7.6 |
| 7-1/2 | 24.2 | 22 | 11 |
| 10 | 30.8 | 28 | 14 |
| 15 | 46.2 | 42 | 21 |
| 20 | 59.4 | 54 | 27 |
| 25 | 74.8 | 68 | 34 |
| 30 | 88 | 80 | 40 |
Induction motors; the calculator also has the 115, 200, 575 and 2,300 volt columns and sizes up to 500 horsepower.
Wire and breaker
The branch-circuit conductors for one motor must carry at least 125 percent of the table current (Section 430.22). The breaker or fuse that protects against short circuits and ground faults may be no larger than a percentage of the table current set by Table 430.52: 250 percent for an inverse time breaker, 175 percent for a dual-element time-delay fuse and 300 percent for a nontime-delay fuse, for single-phase motors and three-phase motors other than wound-rotor. Where that figure is not a standard size, the next standard size up is allowed, and if the motor still will not start, Exception No. 2 allows more. Overload protection is a separate device, sized from the nameplate.
Questions people ask
How many amps does a 1 hp motor draw at 230 volts?
The code's table gives 8 amps for a single-phase motor, 4.2 for a three-phase one.
Should I use the nameplate amps or the table?
The table, for the wire and for the breaker or fuse. The nameplate current is for the overload protection.
How big can the breaker for a motor be?
Up to 250 percent of the table current for an inverse time breaker, or the next standard size above that figure.