Trap Arm Length Calculator
Pick the trap size and, if you like, enter how far the vent is from the trap. The calculator gives the longest trap arm allowed by the 2021 International Plumbing Code and the slope it has to keep.
Longest trap arm
6 ft
- Trap size
- 1-1/2 in
- Slope of the fixture drain
- 1/4 in per ft
- Fall over the full length
- 1.5 in
IPC 2021 Section 909.1 and Table 909.1.
The trap arm is the stretch of drain between a fixture's trap and its vent. For a 1-1/2 inch trap, IPC Table 909.1 allows at most 6 feet at a slope of 1/4 inch per foot.
What the trap arm is
Every fixture has a trap, the U-shaped bend that holds water and keeps sewer gas out of the house. The pipe that leaves the trap and runs to the point where the vent connects is the trap arm, or fixture drain. Section 909.1 of the IPC says the slope and the developed length of that pipe, measured from the trap weir to the vent fitting, must stay within Table 909.1.
The weir is the top of the trap's outlet, where the water spills over. Measure from there, along the pipe, to the vent fitting.
The limits in Table 909.1
- 1-1/4 inch trap: 5 feet, at 1/4 inch per foot.
- 1-1/2 inch trap: 6 feet, at 1/4 inch per foot.
- 2 inch trap: 8 feet, at 1/4 inch per foot.
- 3 inch trap: 12 feet, at 1/8 inch per foot.
- 4 inch trap: 16 feet, at 1/8 inch per foot.
The minimum trap size for each fixture is set elsewhere in the code, and it changes between codes and local amendments, so check it with your inspector before you size the arm.
A worked example
A 1-1/2 inch trap under a sink drains toward a vent 4.5 feet away. Table 909.1 allows up to 6 feet for that trap size, at a slope of 1/4 inch per foot, so the layout is within the limit. Over the full 6 feet that slope adds up to 1.5 inches of fall.
When the vent is too far
If the vent connects farther from the trap than the table allows, the usual fixes are to move the vent closer, to add a vent nearer the fixture or, where the code allows it, to use another venting method. A longer arm cannot be fixed by adding slope: the table sets both limits together.
Questions people ask
How far can a P-trap be from the vent?
It depends on the trap size: from 5 feet for a 1-1/4 inch trap to 16 feet for a 4 inch trap, under IPC Table 909.1, measured along the pipe from the trap weir to the vent fitting.
Does the vertical drop of a sink tailpiece count?
The table measures the fixture drain from the trap weir to the vent fitting, so the part above the trap does not count. What counts is the pipe after the trap.