Expansion Tank Sizing Calculator

Enter the size of the water heater, the static supply pressure and the temperature it is set to. The calculator reads AMTROL's quick sizing chart for its Therm-X-Trol tanks and explains when the plumbing code requires a means of controlling thermal expansion.

Tankless and point-of-use heaters up to 2 gallons: enter their size.

The pressure with no water running.

AMTROL Therm-X-Trol model

ST-5

Chart row and column
50 gallons, 60 psi, 140 °F table
Tank volume
2 gallons
Precharge
set to 60 psi, the static supply pressure

The chart assumes 40 °F incoming water and a 150 psi temperature and pressure relief valve on the heater.

AMTROL Therm-X-Trol brochure MC4090 (09/25), quick sizing charts.

Heated water expands, and in a closed system the pressure rises. For a 50 gallon heater at 60 psi set to 140 °F, AMTROL's chart gives the ST-5.

When you need one

Section P2903.4 of the residential code requires a means of controlling the pressure from thermal expansion in two cases: where a pressure-reducing valve is installed and expansion raises the pressure downstream of it above its setting, and where a backflow prevention device, check valve or similar device is installed on a system with a storage water heater so that thermal expansion raises the pressure. An expansion tank is one such means.

Reading the chart

AMTROL's quick sizing chart picks a tank from three figures: the water heater's size in gallons, the static supply pressure in psi and the maximum temperature setting, with separate tables for 140, 160 and 180 °F. It assumes 40 °F incoming water and a 150 psi temperature and pressure relief valve. A hotter setting or a higher pressure calls for a larger tank, because the water expands more and the tank has less room to take it.

AMTROL Therm-X-Trol at 140 °F.
Heater40 psi60 psi80 psi
40 galST-5ST-5ST-5
50 galST-5ST-5ST-5
60 galST-12ST-12ST-12
80 galST-12ST-12ST-12
120 galST-12ST-12ST-25V

The ST-5 holds 2.0 gallons, the ST-12 4.4 and the ST-25V 10.3. Tankless and point-of-use heaters up to 2 gallons take the ST-1. Between the chart's rows and columns, the calculator uses the next larger one.

A worked example

A 50 gallon water heater set to 140 °F is on a system with a check valve, at a static pressure of 60 psi. In AMTROL's 140 °F table, the 50 gallon row and the 60 psi column give the ST-5, a 2 gallon tank, with its precharge set to 60 psi. At 160 °F the same heater would need the larger ST-12.

Precharge

AMTROL's chart assumes the tank's air precharge is set equal to the static supply pressure, for the ST-5 and larger. Its tanks leave the factory at a fixed precharge, so check it and adjust it to your pressure before installing.

Questions people ask

Do I need an expansion tank on my water heater?

The residential code requires a way to control thermal expansion where a pressure-reducing valve, a check valve or a backflow preventer closes the system, so that heating the water raises the pressure. An expansion tank is the usual way.

What size expansion tank for a 50 gallon water heater?

With AMTROL's chart at 140 °F, the ST-5 at 40 to 80 psi. At 160 °F, the ST-5 up to 40 psi and the ST-12 at 60 or 80 psi; at 180 °F, the ST-12.

What should the expansion tank pressure be?

AMTROL sizes its tanks with the precharge equal to the static water supply pressure.

Sources