Whole-House Ventilation Calculator

Enter the floor area and the number of bedrooms. The calculator works out the minimum whole-house mechanical ventilation rate of the 2021 International Residential Code, from both its table and its equation, and adjusts it for the 30 percent credit and for a fan that runs only part of the time.

Exception 1 of M1505.4.3 lowers the rate by 30% when both conditions are met.

100 for a fan that runs all the time. The code allows down to 25% with a programmed control.

Minimum continuous ventilation

50 cfm

Table M1505.4.3(1)
60 cfm (1,501 to 3,000 sq ft, 2-3 bedrooms)
Equation 15-1
0.01 × 2,000 + 7.5 × (3 + 1) = 50 cfm

The code accepts either the table or the equation, so the lower of the two is the minimum.

Separately, kitchens need 100 cfm intermittent or 25 cfm continuous exhaust, bathrooms 50 or 20 cfm (Table M1505.4.4).

2021 IRC Section M1505.4.3, Table M1505.4.3(1), Equation 15-1 and Table M1505.4.3(2).

A 2,000 sq ft house with 3 bedrooms needs at least 50 cfm of outdoor air, continuously: the table gives 60 cfm and Equation 15-1 gives 50 cfm, and the code accepts either.

When the code asks for it

Section R303.4 requires mechanical ventilation in accordance with Section M1505, or other approved means of ventilation, for buildings and dwelling units that comply with Section N1102.4.1, the air leakage rules of the energy chapter. Those rules require the dwelling to be tested for air leakage, with a maximum of 5.0 air changes per hour or 0.28 cfm per square foot of dwelling unit enclosure area, reported at a pressure of 50 pascals. A whole-house system is one or more supply or exhaust fans, or both, with their ducts and controls; local exhaust or supply fans may serve as the system, and outdoor air ducted to the return side of an air handler counts as supply ventilation.

Table or equation

Section M1505.4.3 asks for outdoor air at a continuous rate not less than the one in Table M1505.4.3(1) or not less than the one from Equation 15-1:

cfm = 0.01 × floor area + 7.5 × (bedrooms + 1)

Either satisfies the code, so the minimum is the lower of the two, and the calculator shows both. The table steps by floor area and by pairs of bedrooms; the equation follows the house exactly and often comes out lower.

Continuous whole-house ventilation airflow in cfm by floor area (sq ft) and bedrooms, Table M1505.4.3(1).
Sq ft0-12-34-56-7Over 7
Under 1,5003045607590
1,501–3,00045607590105
3,001–4,500607590105120
4,501–6,0007590105120135
6,001–7,50090105120135150
Over 7,500105120135150165

The table's first row is under 1,500 sq ft and its second starts at 1,501, so a house of exactly 1,500 sq ft falls between them. The calculator reads it in the second row, the larger rate, and does the same for any area above a row's upper figure.

The 30 percent credit

Exception 1 lowers the rate by 30 percent when both conditions apply: a ducted system supplies ventilation air directly to each bedroom and to the living room, the dining room or the kitchen, and the system is balanced.

Fans that do not run all the time

Exception 2 allows intermittent operation where the controls run the system for at least 25 percent of each 4-hour segment. The continuous rate, after the credit if it applies, is then multiplied by a factor from Table M1505.4.3(2):

Intermittent ventilation factors, Table M1505.4.3(2).
Run time in each 4-hour segmentFactor
25%4
33%3
50%2
66%1.5
75%1.3
100%1.0

Between the listed run times the code permits interpolation, and the calculator interpolates in a straight line. Extrapolation beyond the table is prohibited, so the calculator gives nothing under 25 percent.

A worked example

A 2,000 sq ft house has 3 bedrooms, and its ventilation fan is on a timer that runs it half of each 4-hour period.

  • Table M1505.4.3(1): 60 cfm (1,501 to 3,000 sq ft, 2 to 3 bedrooms).
  • Equation 15-1: 0.01 × 2,000 + 7.5 × (3 + 1) = 50 cfm, the lower of the two.
  • At 50% run time the factor is 2, so the fan must move 100 cfm while it runs.

Kitchen and bathroom exhaust

Local exhaust is a separate requirement, in Table M1505.4.4: a kitchen needs 100 cfm intermittent or 25 cfm continuous, and a bathroom or toilet room 50 cfm intermittent or 20 cfm continuous. Exhaust fans and whole-house ventilation fans must be listed and labeled for their airflow under ANSI/AMCA 210-ANSI/ASHRAE 51, and a bathroom fan's listed rate must be met at a static pressure of at least 0.25 inch of water column. The whole-house system needs controls with a manual override, marked with text or a symbol that shows what they do.

Questions people ask

How many cfm of fresh air does a house need?

Under the residential code, the lower of Table M1505.4.3(1) and Equation 15-1. For a 2,000 sq ft house with 3 bedrooms that is 50 cfm, continuously.

Can a bathroom fan be the whole-house ventilation?

Section M1505.4.1 allows local exhaust or supply fans to serve as the whole-house system. The fan still has to deliver the required rate, be listed and labeled for its airflow, and have controls with a manual override.

Is this the ASHRAE 62.2 rate?

No. This calculator uses the International Residential Code's own table and equation. ASHRAE Standard 62.2 is a separate document, and we have not used it here.

What does the 30 percent credit require?

Both a ducted supply of ventilation air to every bedroom and to the living room, the dining room or the kitchen, and a balanced system. With both, the rate drops by 30 percent.

Sources