Sill & Rafter

Heating, Cooling & Energy · Calculator

Duct CFM and Supply Register Calculator

Enter the size of the system and its airflow per ton. Add a room's design load and the whole house's to get the room's airflow, then pick a register and a face velocity to see how many registers it takes.

The nominal cooling capacity: 12,000 Btu/h is one ton.

Use the setting in your equipment's instructions. Makers design for 350 to 450; about 400 is the usual recommendation.

From a Manual J load calculation, room by room. Leave empty for the whole house.

The same Manual J, total for all rooms, in the same mode (heating or cooling) as the room.

Capacities published by Hart & Cooley for its 661 wall register and 421 floor diffuser.

Air speed through the register face. Faster moves more air but makes more noise.

Registers for the house

10 registers

System
3 tons (36,000 Btu/h)
Blower airflow
1,200 CFM
One register at 700 fpm
120 CFM

The register count is rounded up. With fewer registers each one must run faster and louder.

This is a count for the whole house. Rooms do not need equal air: enter a room's load to size it.

Duct sizes and the blower's real airflow come from a Manual D design and the maker's fan tables, not from this count.

Daikin and FSEC on airflow per ton; Hart & Cooley engineering data; ACCA room share.

A 3 ton system at 400 CFM per ton moves 1,200 cubic feet of air a minute. A room with 12.5 percent of the design load gets 150 CFM, which takes 2 floor diffusers of 4 by 10 inches at 700 feet per minute.

Airflow per ton

A ton of cooling is 12,000 Btu per hour. Daikin's installation instructions say most cooling systems are designed for 350 to 450 cubic feet per minute (CFM) per ton, and that most makers recommend about 400; its own example is 2.5 tons × 400 = 1,000 CFM. The same instructions tell the installer to check the equipment maker's required airflow, so use that figure when you have it. ACCA notes that in hot, humid climates a lower airflow, such as 350 CFM per ton, can keep the house comfortable.

Real systems often move less than they should. The Florida Solar Energy Center measured 27 homes and found 130 to 510 CFM per ton, an average of 320, with undersized return ducts, wrong fan speeds and dirty filters and coils among the causes.

Each room's share

Rooms do not get equal air. In the design method of the Air Conditioning Contractors of America (ACCA), each room gets the blower's airflow in proportion to its share of the house's load from a Manual J calculation: room CFM = blower CFM × room load ÷ total load. Do it once with the heating loads and once with the cooling loads, and size the duct run for the larger. In ACCA's example a room with 4,800 of 48,000 Btu/h of cooling and 5,800 of 60,000 Btu/h of heating, on a 1,000 CFM blower, gets 100 CFM for cooling and 97 for heating, so it is designed for 100.

ENERGY STAR new homes follow the same path: room-by-room loads from Manual J, ducts designed with Manual D, and each room's measured airflow within 20 percent or 25 CFM of the design, whichever is greater.

How much air a register moves

A register's airflow is its free area times the speed of the air through its face. Hart & Cooley recommends sizing supply outlets for 500 to 800 feet per minute, with 700 a common target; faster air is noisier. Its published capacities, in CFM:

Register500 fpm600 fpm700 fpm
Wall, 10 × 4 in (661)7585100
Wall, 12 × 4 in (661)90110125
Wall, 10 × 6 in (661)125145170
Floor, 4 × 10 in (421)85100120
Floor, 4 × 12 in (421)100120140
Floor, 6 × 10 in (421)120145170

Other models and makers differ: their engineering data has the figures.

What this count does not do

It does not size the ducts. Daikin asks for ducts sized for 350 to 450 CFM per ton with the external static pressure no higher than 0.5 inches of water, and refers to ACCA Manual D for the design. The blower's real airflow depends on that static pressure and comes from the maker's fan tables.

Questions people ask

How many CFM per ton?

Makers design for 350 to 450 CFM per ton, and most recommend about 400. Your equipment's instructions give the setting for your unit.

How much air does a 4 by 10 floor register move?

Hart & Cooley's 421 floor diffuser in 4 by 10 inches moves 85 CFM at 500 feet per minute, 100 at 600 and 120 at 700.

How do I know how much air a room needs?

From a room-by-room Manual J load calculation: the room gets the blower's airflow times its share of the total load. Rules of thumb per square foot are not part of the ACCA method.

How many supply registers does a room need?

Enough to carry the room's airflow at a face velocity that stays quiet, usually 500 to 700 feet per minute. In the example above, a room needing 150 CFM takes 2 floor diffusers of 4 by 10 inches at 700 feet per minute.

Sources