Sill & Rafter

Electrical · Calculator

Wire Resistance Calculator

Choose the wire size, the metal and the length of the run. The calculator reads the conductor's resistance from the National Electrical Code's Table 8, corrects it for temperature and, if you add the current, shows the voltage lost along the wire.

Solid wire is listed only up to 8 AWG. Larger sizes are always stranded.

One way, from the panel to the load.

A two-wire circuit carries current out on one conductor and back on the other.

The code table is at 75 °C. A lightly loaded wire runs cooler.

Optional.

Resistance of the run

0.386 ohm

Table 8 at 75 °C
1.93 ohm per 1,000 ft (solid copper)
At 75 °C
1.93 ohm per 1,000 ft
Conductor length
200 ft

NEC 2014 Chapter 9, Table 8 and its Note 2 (dc resistance).

Wire resistance depends on the size, the metal, the length and the temperature. 100 feet of 12 AWG solid copper, out and back, has 0.386 ohm at 75 °C, so a 16 amp load loses 6.2 volts along the way.

Where the numbers come from

Chapter 9 of the National Electrical Code has a table of conductor properties, Table 8, that lists the direct-current resistance of every common wire size in ohms per 1,000 feet, at a conductor temperature of 75 °C. The calculator uses the 2014 edition of that table, for uncoated copper and for aluminum, solid and stranded.

Solid wire is listed only up to 8 AWG; bigger sizes are always stranded. Stranded wire has slightly more resistance than solid of the same size, because the strands do not fill the circle completely. Aluminum has roughly 1.6 times the resistance of copper of the same size: 12 AWG solid copper is 1.93 ohm per 1,000 feet, 12 AWG solid aluminum 3.18.

Correcting for temperature

Metal resists more as it warms up. Note 2 under Table 8 gives the correction: multiply the table value by 1 + a × (T − 75), where T is the conductor temperature in °C, and a is 0.00323 for copper and 0.00330 for aluminum. A lightly loaded wire in a cool space runs well below 75 °C and has a little less resistance than the table; a wire near its limit runs hotter.

A worked example

A 100 foot run of 12 AWG solid copper feeds a 120 volt load. Out and back, the current travels 200 feet of wire. Table 8 gives 1.93 ohm per 1,000 feet at 75 °C, so the run has 0.386 ohm. At 16 amps, that is 6.2 volts lost in the wire, more than the 3 percent the code's informational note suggests for a branch circuit on 120 volts.

From resistance to voltage drop

Current times resistance gives the volts lost along the wire. Remember that a two-wire circuit carries the current out and back, so the conductor length is twice the distance from the panel to the load. Choose out and back for that; choose one conductor when you want the resistance of a single wire.

The NEC's informational notes suggest keeping the voltage drop of a branch circuit to about 3 percent and the total of feeder and branch circuit to about 5 percent, for reasonable efficiency. They are recommendations, not requirements.

This is the direct-current resistance. For alternating current in large conductors and in metal conduit, the code's Table 9 adds the effects of reactance; for the small sizes used in house wiring the difference is small.

Questions people ask

What is the resistance of 12 gauge copper wire?

Solid 12 AWG copper is 1.93 ohm per 1,000 feet at 75 °C in NEC Table 8; stranded is slightly higher. For a run, multiply by the length in thousands of feet, and double it for a circuit that goes out and back.

Does aluminum wire have more resistance than copper?

Yes, about 1.6 times as much for the same size. That is why an aluminum conductor is usually a larger size than the copper it replaces.

Why does the result change with temperature?

Because the resistance of metal rises as it warms. Table 8 is at 75 °C; Note 2 under the table gives the correction the calculator applies.

Sources