Choose what you know, enter the line-to-line voltage and the power factor, and the calculator gives the line current or the power of a balanced three-phase load.

Common three-phase voltages are 208, 240 and 480 V.

Between 0 and 1. Use 1 for heaters; motors are often lower.

Line current

66.8 A

Voltage, line to line
480 V
Power factor
0.9
Apparent power
55.56 kVA
Real power
50 kW
Line current
66.8 A

VA = A × V × √3 (NEC 2014 Annex D, Example D3(a)); kW = kVA × power factor.

On a balanced three-phase system, apparent power equals the line current times the line-to-line voltage times the square root of 3. A 50 kW load at 480 volts with a power factor of 0.9 draws 66.8 amps per line.

The formula

kVA = A × V × √3 ÷ 1,000
kW = kVA × power factor
A = kW × 1,000 ÷ (V × √3 × power factor)

V is the voltage between any two lines, A the current in each line. The National Electrical Code uses the same relation in its worked examples: Annex D multiplies the 3 amp current of a grinder motor at 480 volts by √3 to get 2,490 volt-amperes.

Why the square root of 3

In a three-phase system the three line voltages are out of step with each other, so the voltage between two lines is √3, about 1.732, times the voltage from each line to neutral on a wye system, such as 208Y/120 or 480Y/277 volts. The factor carries over to power: three lines each carrying the same current deliver √3 times the product of the line voltage and the line current.

kW, kVA and power factor

kVA is the apparent power, what the wires and the transformer have to carry. kW is the real power, what the load turns into heat or motion. The power factor is the ratio between them, a number between 0 and 1: heaters run close to 1, while motors and other inductive loads run lower. A lower power factor means more current for the same real power, so wires and breakers are sized on the current, not on the kW.

A worked example

A 50 kW load runs on 480 volt three-phase with a power factor of 0.9. The apparent power is 50 ÷ 0.9 = 55.6 kVA, and the current is that divided by 480 volts and √3: 66.8 amps in each line.

Questions people ask

How do you calculate three-phase amps?

Divide the power in watts by the line-to-line voltage, by √3 and by the power factor. With kVA instead of kW, leave out the power factor.

Is three-phase current the same in every wire?

On a balanced load, yes: each line carries the same current, and that is the current the calculator gives. Unbalanced loads need each phase worked out separately.